PF2100
Modbus Card Instruction Manual v1.1
©2011 Profire Energy Inc
Jan 5, 2012
Page 19
Appendix C – Modbus Register Numbers
The following tables list all of the PF2100 Register Numbers that are accessible via the Modbus Card interface.
Discrete Table
The following registers are all 1-bit in size and are read only in the current firmware version. A future firmware revision may enable some of these to be
writable.
Register #
Register Name
Values
10001
RUN
0 = OFF
10002
Pilot
0 = OFF
10003
Low Fire
0 = OFF
10004
High Fire
0 = OFF
10017
Level Input
0 = Closed
10018
Main Solenoid
Feedback
0 = Off
10019
Pilot Solenoid Feedback
0 = Off
10020
High Pressure Input
0 = Closed
10021
Proof of Closure
0 = Closed
10022
ESD Input
0 = Closed
10023
Start Input
0 = Closed
10024
Low Pressure
0 = Closed
10025
Flame Detected
0 = No Flame
10026
Flame Test Fail
0 = Flame Test OK
10027
Unit Failure
0 = Unit OK
10028
Low or High voltage
0 = Voltage OK
10029
High Temperature Alarm
0 = No Alarm
Analog Tables
The following registers are all 16-bit in size and are read only in the current firmware version.
The registers are all mirrored between two different tables (the 30000 Input Register Table and the 40000 Output Holding Register Table). It has been observed
that some PLCs do not allow bit masks to be applied to some tables but do allow it on others. This is the reason for mirroring the registers between two tables.
A future firmware revision may enable some of the 40000 series registers to be writable.